Industrial cybersecurity basics: protecting controllers and OT networks with IEC 62443

Factories used to be safe because their networks were isolated. Now machines report to business systems, suppliers need remote access and data flows to the cloud. Every new connection is useful, and every one is a possible way in. OT (operational technology) security keeps production running while the plant becomes connected.
At Timeus Lab we design connections between the shop floor and IT with security built in. This guide covers the basics.
Why is OT security different from IT security?
OT security is different because availability and safety come first. An office computer can be restarted for an update; a controller running a furnace cannot. Many industrial devices run for decades, cannot be patched easily and use protocols designed without security. So protection relies more on network design, access control and monitoring than on frequent updates.
What is IEC 62443?
IEC 62443 is a family of international standards for the security of industrial automation and control systems. It covers the responsibilities of plant owners, integrators and product vendors, and introduces ideas such as zones, conduits and security levels. It is the common reference for OT security projects in Europe and beyond.
What are zones and conduits?
Zones are groups of devices with similar security needs, such as one production line or the safety system. Conduits are the controlled connections between zones. Instead of one flat network, the plant is split so that a problem in one zone cannot spread freely to others, and every crossing between zones is known and filtered.
Which measures give the most protection first?
- Separate the control network from the office network, with a controlled zone in between for data exchange.
- No direct internet access to controllers.
- Secure remote access, through one gateway with personal accounts, multi-factor sign-in and logs, opened only when needed.
- Backups of every PLC, HMI and drive program, stored offline and tested.
- An inventory of devices, with versions and owners.
- Monitoring of the control network for unknown devices and unusual traffic.
- Secure protocols where devices support them, such as OPC UA with encryption.
What about regulation?
In the EU, the NIS2 directive raises security duties for many operators in sectors such as energy, transport, manufacturing of critical products and others. Requirements depend on the sector and size, so each company should check whether it falls in scope. IEC 62443 is a practical way to organise the technical measures.
Questions
Is a firewall between office and factory enough?
It is a good start, not the end. Remote access, removable media, supplier laptops and unmanaged devices are common ways around a single firewall.
Can we patch our PLCs?
Sometimes, in planned windows and after testing. Where patching is not possible, network separation and monitoring reduce the risk.
Does connecting machines to the cloud make them unsafe?
Not if it is designed well. Data can leave the plant through one controlled path, while nothing from outside can reach the controllers. See connecting old machines.